MODEL PRO901-WS/WL PRO902-WS/WL PRO903-WS/WL PRO906-WS/WL PRO910-WS/WL
PHASE Single phase with ground
CAPACITY * 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W 6000VA / 4800W 10000 VA / 8000 W
INPUT
Nominal Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC 208/220/230/240VAC
Input Voltage Range 55-150 VAC or 110-300 VAC (Based on load at 50%) 85-140VAC or 160-280VAC (Based on load at 100%) 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%)
Frequency Range 40 Hz  ~ 70 Hz 46~54 Hz or 56~64 Hz
Power Factor ¨R0.99 @ Nominall Voltage (100% load)
OUTPUT
Output Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC 208/220/230/240VAC
Voltage Regulation ± 1 %
Frequency Range (Synchronized Range) 47~ 53 Hz or 57 ~ 63 Hz 46~54 Hz or 56~64 Hz
requency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 50 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ¨Q 3 % THD (Linear Load)
¨Q 6 % THD (Non-linear Load)
¨Q 3 % THD (Linear Load)
¨Q 5 % THD (Non-linear Load)
Transfer Time AC Mode to Battery Mode Zero
Inverter to Bypass 4 ms (Typical) Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode 88% 88% 90% 92% 93%
Battery Mode 83% 87% 88% 90% 91%
BATTERY
 
 

Standard Model
Battery Type 12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah
Numbers 2 4 6 16 20 16 20
Typical Recharge Time 4 hours recover to 90% capacity 9 hours recover to 90% capacity
Charging Current (max.) 1 A 1 A / 2 A
Charging Voltage 27.4VDC ± 1% 54.7 VDC ±1% 82.1 VDC ±1% 218.4 VDC
±1%
273VDC ±1% 218.4 VDC
±1%
273VDC ±1%
 
Long-run Model **
Battery Type Depending on the capacity of external batteries
Numbers 2 3 4 6 8 6 8 16 ~ 20 (Adjustable)
Charging Current (max.) 1A/2A/4A/6A (Adjustable) 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries)
Charging Voltage 27.4VDC ± 1% 41.0VDC ± 1% 54.7 VDC ±1% 82.1 VDC ±1% 109.4VDC ±1% 82.1 VDC ±1% 109.4VDC ±1% 273 VDC ±1% (Based on 20pcs batteries)
INDICATORS
LCD Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model Dimension, D x W x H(mm) 282 x 145 x 220 397 x 145 x 220 421 x 190 x 318 369 x 190 x 688 442 x 190 x 688
Net Weight (kgs) 9.8 17 27.6 61 74 66 76
Long-run Model ** Dimension, D x W x H(mm) 282 x 145 x 220 397 x 145 x 220 369 x 190 x 318 442 x 190 x 318
Net Weight (kgs) 4.1 6.8 7.4 12 16
ENVIRONMENT
Humidity 20-90 % RH @ 0- 40°C (Non-condensing) 0-95% RH @ 0-50°C
(non-condensing)
0-95% RH @ 0-40°C
(non-condensing)
Noise Level Less than 50dBA @ 1 Meter Less than 55dBA @ 1 Meter Less than 58dBA @ 1 Meter
MANAGEMENT
Smart RS-232 / USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix and MAC
Optional SNMP Power management from SNMP manager and web browser